Home |
Automotive Testing Products |
Conditioned Air Supply Systems |
Drive In Chambers |
HVAC Testing Products |
Environmental Rooms |
Custom Air Handlers |
Careers |
|
|
|
ULTRA-LOW TEMPERATURE WALK-IN FREEZER CTS manufactures custom designed walk-in, ultra-low temperature freezers that are used for the storage of biological specimens or pharmaceutical products. Our walk-in ULTs are ideal for Repository applications or Long Term Storage and Shipping operations where the space and maintenance required for dozens of small reach units has become a problem. CTS walk-in ULTs will maintain the freezer chambers to a temperature as low as -80°C (-112° F) on a continuous basis. The ULT Freezer is constructed from modular, urethane insulated panels with cam-locks for easy assembly. The support equipment for the freezer will include redundant, cascade refrigeration systems, Programmable Logic Controller (PLC), and liquid nitrogen backup system. The typical ULT Freezer includes a double wall design to prevent moisture on the outside of the freezer. A +4°C anteroom leads to a corridor that is maintained at -20°C. ULT freezer compartments are located on both sides of the corridor. The freezer compartments are accessed from the corridor so that personnel do not enter the -80°C space. The overall freezer layout can be designed to match your existing space to provide maximum flexibility. |
|
| |||
| Typical Performance Specifications | |||
| Parameter | Range | Stability | |
|
| |||
| Anteroom Dry Bulb Temperature | +4°C | ± 0.5°C | |
|
| |||
| Anteroom Dew Point Temperature | < -73°C | Not Controlled | |
|
| |||
| Corridor Dry Bulb Temperature | -20°C | ± 0.5°C | |
|
| |||
| ULT Freezer Dry Bulb Temperature | -70°C to -80°C | ± 0.5°C | |
|
| |||
| Temperature
Uniformity - ULT Freezer Compartments - Corridor - Anteroom |
± 3°C ± 2°C ± 1°C |
||
|
| |||
| Key Features | ||
| > | Independent, Redundant Cascade Refrigeration Systems utilizing Copeland Scroll or Bitzer Screw Compressors | |
| > | Liquid Nitrogen Backup System | |
| > | Dual Chamber Configuration for maximum 'R' value | |
| > | Redundant Gravity Cooling Coils | |
| > | Dry Air Purge minimize frost accumulation | |
| > | Allen-Bradley Programmable Logic Controller with A-B PanelView Interface | |
| > | Personnel Safety Alarms | |
|
|
||
| Options | ||
| > | Yokogawa Temperature Recorder | |
| > | UPS for controls | |
| > | Oxygen Monitor | |
| The specifications shown above are typical. Climatic Testing Systems, Inc. can customize your system to provide the performance that you desire. | ||
|
|
|
Home | Automotive Testing Products | Conditioned Air Supply Systems | Drive In Chambers | HVAC Testing Products | Environmental Rooms | Custom Air Handlers | Contact Us | Careers |
|
|
|
Climatic Testing Systems | Phone: 215-773-9322 | Fax: 215-773-9323 |